Drawing Specification Worksheets
Note: These PDFs may open as a new tab in your web browser rather than opening in Adobe Reader. The “Submit” button will only work in Adobe Reader. If the submit button does not do anything when clicked, save the PDF and re-open it in Adobe Reader. The submit button will create a new email in your default email client to sales@canadiancoiltech.com with the PDF attached. Alternatively, you may manually send the PDF as an attachment to sales@canadiancoiltech.com.
- Condenser Coil Worksheet (PDF)
- Evaporator Coil Worksheet (PDF)
- Replacement Coil Template (PDF)
- Steam Coil Worksheet – Opposite End (PDF)
- Steam Coil Worksheet – Same End (PDF)
- Water Glycol Coil Worksheet (PDF)
Operating Condition Worksheets
- Condenser Coil Short Info
- Fluid (Cooling) Coil Short Info
- DX (Evaporator) Coil Short Info
- Fluid (Heating) Coil Short Info
- Steam Coil Short Info
Common Formulas
| Face Area (ft2): | FA = FH x FL / 144 |
| Face Velocity (fpm): | FV = SQEM / FA |
| Heating Applications: | SH = 1.085 x SCFM x (DBL – DBE) GPM = SH / 500 x (EWT – LWT) |
| Cooling Applications: | TH = 4.5 X SCFM X (HE – HL) SH = 1.085 x SCFM x (DBE – DBL) GPM = TH / 500 X (LWT – EWT) |
| Where: | DBE = Entering air dry bulb (°F.) DBL = Leaving air dry bulb (°F.) EWT = Entering water temperature (°F.) FA = Coil face area (ft2) FH = Finned height (in.) FL = Finned length (in.) FPM = Feet/minute FV = Face velocity (fpm) |
GPM = U.S. gallons/minute of water HE = Enthalpy of entering air (BTU/lb.) HL =Enthalpy of leaving air (BTU/lb.) LWT = Leaving water temperature (°F.) SCFM = Standard cubic feet/minute of air SH = Sensible heat (BTU/hour) Total heat (BTU/hour) |