Resources

Drawing Specification Worksheets

Note: These PDFs may open as a new tab in your web browser rather than opening in Adobe Reader. The “Submit” button will only work in Adobe Reader. If the submit button does not do anything when clicked, save the PDF and re-open it in Adobe Reader. The submit button will create a new email in your default email client to sales@canadiancoiltech.com with the PDF attached. Alternatively, you may manually send the PDF as an attachment to sales@canadiancoiltech.com.

Operating Condition Worksheets

Common Formulas

Face Area (ft2): FA = FH x FL / 144
Face Velocity (fpm): FV = SQEM / FA
Heating Applications: SH = 1.085 x SCFM x (DBL – DBE)
GPM = SH / 500 x (EWT – LWT)
Cooling Applications: TH = 4.5 X SCFM X (HE – HL)
SH = 1.085 x SCFM x (DBE – DBL)
GPM = TH / 500 X (LWT – EWT)
Where: DBE = Entering air dry bulb (°F.)
DBL = Leaving air dry bulb (°F.)
EWT = Entering water temperature (°F.)
FA = Coil face area (ft2)
FH = Finned height (in.)
FL = Finned length (in.)
FPM = Feet/minute
FV = Face velocity (fpm)
GPM = U.S. gallons/minute of water
HE = Enthalpy of entering air (BTU/lb.)
HL =Enthalpy of leaving air (BTU/lb.)
LWT = Leaving water temperature (°F.)
SCFM = Standard cubic feet/minute of air
SH = Sensible heat (BTU/hour)
Total heat (BTU/hour)

Note: On Cooling Applications with dehumidification (wet coils), the face velocity should not exceed 500 fpm to prevent water-carryover from the coil.